Physically separated PCS, transformer, and switchgear chambers prevent thermal coupling and contain internal arc faults per IEC 61330 Annex A; enables safe single-module maintenance without de-energizing adjacent compartments—unavailable in monolithic designs.
Four-quadrant PCS supports PQ/VF/grid-forming modes; synthetic inertia emulation and <20ms fault current injection stabilize weak grids; black-start certified for islanded microgrid energization without external source.
Independent forced-air cooling circuits for PCS and transformer prevent heat stacking; dedicated ventilation maintains PCS junction temperature <85°C at +50°C ambient, preserving semiconductor lifespan and round-trip efficiency >98.5%.
Standardized LV bus interface and Modbus/IEC 61850 protocol abstraction layer enable plug-and-play integration with Tier-1 PCS and battery brands; avoids vendor lock-in and simplifies future repowering.
Each compartment equipped with independent smoke/heat detection and aerosol/gas suppression activation; fire-rated partition walls (EI60) limit propagation; optional K-class fluid or dry-type transformer eliminates oil fire risk.
Class H insulation copper windings for harmonic-rich inverter duty; amorphous alloy core option for 24/7 partial-load efficiency; acrylic rubber gaskets validated for 20-year UV/ozone resistance; tinned copper busbars for corrosion-free high-current connections.
95% automated assembly line with torque-controlled busbar tightening and vacuum-assisted cable termination; CNAS-accredited lab performs routine + type tests including efficiency mapping, harmonic emission, and thermal cycling endurance.
One-piece formed shell eliminates welding seams; 7-layer nano coating passes ISO 12944 C5-M 20,000-hour salt spray test; mechanical impact IK10; seismic Zone 4 qualification available.
| No. | Items | Unit | Value | ||
| 1 | Rated voltage | Primary | 40.5 | ||
| Secondary | kV | 12; 0.69 | |||
| Subsidiary circuit | V | 110; 220; 380 | |||
| 2 | Rated current | High voltage circuit | 400~1250 | ||
| Low voltage circuit | A | 630~3150 | |||
| 3 | Rated frequency | Hz | 50 | ||
| 4 | Rated power | kVA | 1250; 1600; 2000~20000 | ||
| 5 | Rated insulation level | High voltage side | Power frequency | 95 | |
| impact | 185 | ||||
| Low voltage side | Power frequency | 42 | |||
| impact | kV | 75 | |||
| 6 | Rated short time withstand current | High voltage side | 20; 25; 31.5 | ||
| Low voltage side | 25; 31.5; 40 | ||||
| Rated peak withstand current | High voltage side | 50; 63; 80 | |||
| 7 | Low voltage side | kA | 63; 80; 100 | ||
| 8 | Insulation level of transformer | Power frequency | 65 | ||
| Impact | 185 | ||||
| 9 | Insulation level of subsidiary circuit | kV | |||
| 2 | |||||
Configurable DC/AC coupling topology; pre-integrated BMS communication gateway supporting CAN/Modbus TCP/Ethernet-IP; factory-mapped protection coordination with major battery OEMs.
Factory-programmed FFR/SI curves per local TSO requirement; STATCOM mode for nighttime voltage support; SOC-reserved emergency backup logic for critical load priority.
Desert package (G4 sand filtration + enhanced radiator + UV-stabilized coating); Arctic package (trace heating + low-temp lubricants + insulated doors); Tropical package (anti-condensation dehumidifier + fungicide-treated filters).
Per-compartment independent detection + suppression; EI60 fire-rated partitions between chambers; optional water mist system for transformer chamber; battery room interface for early warning signal integration.
IEC 62351 compliant encrypted communication; unidirectional OT/IT gateway; secure boot + firmware signing for embedded controllers; physical tamper-evident seals on all access panels.
Standard ISO container footprint for global shipping; integrated lifting points certified for 4-point sling; pre-assembled MV cable terminations reducing field labor by 60%; split-module option for oversized configurations.
Bilingual nameplates/O&M manuals; FAT report with efficiency curve and harmonic spectrum; BIM-ready 3D model; cybersecurity compliance declaration per NERC CIP/IEC 62443.
Tell us your project requirements—voltage level, environment, grid code, or delivery timeline—and we’ll provide a compliant, optimized solution.